Correct Fire Alarm & Fire Sprinkler Deficiencies

Building 100

  • Replace the 8” Fire-main cross-connect at Bldg. 100 to 101
  • Install EST3 Duct Detectors (minimum of 2 – one in supply and one in the return):
    • Main Atrium Lobby – AHU-B22 located in room B2A-102
    • B1 Pharmacy – AHU-B15 located in B1C-118
    • Day Surgery – AHU-43A/B located on roof above executive office

Building 101

  • Install EST3 Duct Detectors (minimum of 2 – one in supply and one in the return):
    • Auditorium – AHU-5 located in room 134-101
  • Replace Fireman’s standpipe roof valves:
    • B101 Roof above stairwell 14 with PIV
    • B101 Roof above stairwell 15 with PIV
  • Replace fire pump, jockey pump, fire pump controller and backflow for supply for Floors 4 through 9.

Building 102

  • Replace 3 non-addressable pull stations on P1 with addressable EST3 pull stations with weatherproof covers
  • Replace 4 non-addressable pull stations on P2 (3 in garage, one in smokeshack, south end) with addressable EST3 pull stations with weatherproof cover

Building 1

  • Survey sprinkler system and sprinklers and design a replacement of obsolete sprinklers and related equipment.

Building 2

  • Survey sprinkler system and sprinklers and design a replacement of obsolete sprinklers and related equipment

Building 11

  • Survey sprinkler system and sprinklers and design a replacement of obsolete sprinklers and related equipment

Fire Hydrant replacement

  • Bldg. 102, P2 entrance
  • Hydrant located South of trailer #1

Hazmat Shed Fire Suppression System Replacement

  • Install one Amerex Industrial System 35ABC Fire Suppression System or equivalent in accordance with NFPA 17. Pull station to be relocated near entry door. (system must be compatible with EST3) 

Radiation Shed Fire Suppression System Replacement 

  • Install one Amerex Industrial System 35ABC Fire Suppression System or equivalent in accordance with NFPA 17. Pull station to be relocated near entry door. (system must be compatible with EST3)